		I did a recent inspection with a Hot tub and everything about the circuit was wrong. 
I wanted to ask/discuss my findings and if there are any other issues/requirements for the circuit. My findings. No disconnect within 6 feet of Tub. No GFCI protection. Cable improperly secured, installed at main panel, sub floor and exterior. BX cable used at exterior and noted as a trip hazard and not rated for exterior usage. Here are a few pics and just wanted to know for next time if anything else to document.  | 
					
| 
							 Please Log in to join the conversation. 
		Home Safe Home Inspections 
Link Url: Cleveland Home Inspector - www.hshinspections.net/ Body:Performing Home Inspections in Cleveland, Parma, Brecksville, Broadview Heights, North Royalton, Strongsville and surrounding areas. Keywords:Parma,Broadview...  | 
					
							
  | 
						
							
 
		I think you covered it, unless those conductors are entering some duct work in the 2nd photo. 
Looks like an amateur install all the way around.  | 
					
| 